Instruction Manual
55100 ELECTRONIC LEAK DETECTOR
Gebrauchsanweisung
55100 ELEKTRONISCHE LECKSUCHER
Manuel d’Instructions
55100 DETECTEUR ELECTRONIQUE DE FUITES
Manual de Instrucciones
55100 DETECTOR ELECTRÓNICO DE FUGAS
Visit us at www.TestEquipmentDepot.com
Français
Español
99 Washington Street
Melrose, MA 02176
Phone 781-665-1400
Toll Free 1-800-517-8431
English
Deutsch
Related Manuals for MasterCool 55100
Summary of Contents for MasterCool 55100
����������
�������������
��
�����
����������
���
�������������
��
���
SENSITIVITY
Made in USA
SENSITIVITY
Made in USA
BATTERY TEST
Turning the unit ON will automatically run the battery function test
and display the battery condition on the UNITS LED display. To view
the remaining battery life, press and hold the ON/OFF button.
1. SENSITIVITY LEVELS
55100 offers three sensitivity levels (Low-Med-High). It will detect leaks as low as 1/10 oz (3 grams) per
year. Turn ON the unit, it will default to the Medium Level. (The Medium Level is the recommended setting to
begin inspection). To view the sensitivity level on the LED display, press either the UP or DOWN arrow. The
LED display will illuminate for approximately two seconds. Two Red LEDS will progressively illuminate for
every sensitivity level.
Low Sensitivity
Setting
The sensitivity level can be increased by the UP arrow and decreased by the DOWN arrow. Pressing the
selected arrow once will adjust the sensitivity to the next level. Pressing and holding the arrow will continue
to move the setting until the arrow is released.
2. DETECTION LEVELS
55100 offers 5 levels of detection. As the unit approaches the leak source and the refrigerant concentration
increases, the audible alarm will increase in speed and the LED will display 5 levels of detection.
The detection level will vary depending on the level of the sensitivity setting. The same size leak will display
higher detection levels in higher sensitivity settings and lower detection levels in the lower sensitivity
settings.
3. RESET FUNCTION
The primary use for the RESET function is to pinpoint the leak source. When the unit detects a leak and goes
into full alarm, press the RESET button. Resetting will ignore any leaks at that level and only detect leaks of
higher concentration.
IMPORTANT LEAK DETECTION TIPS:
A. Make sure that the air conditioning/refrigeration system is turned OFF before inspection. A sufficient
amount of refrigerant must be present in the system. A minimum gauge pressure of 50 PSI at ambient
temperature of 60˚ and above with the system OFF is required for efficient leak detection.
2
����������
�������������
��
�����
KEYPAD FUNCTION & PARTS
���
1. Turns unit ON and OFF
����������
�������������
2. Resets Sensitivity Level
to Zero Reference
�����
��
�����
BATTERY INSTALLATION
���
SENSITIVITY
Hold the leak detector handle horizontally.
To remove the battery door, loosen the screw on top of the door and
Made in USA
pull the door away from the unit. Load the two «C» cell batteries into the
compartment with the positive (+) end up. Reinstall the battery door.
SENSITIVITY
Made in USA
Medium
Sensitivity
Setting
Detection Levels
3. Increases Sensitivity
4. Decreases Sensitivity
5. Sensor Tip
GOOD / GREEN
LOW / YELLOW
REPLACE / RED
High Sensitivity
Setting
Highest Levels
English
2
www.mastercool.com
SENSITIVITY
Made in USA
���
����������
�������������
��
�����
BATTERY TEST
Turning the unit ON will automatically run
the battery function test and display the
battery condition on the UNITS LED display.
To view the remaining battery life, press
and hold the
ON/OFF button.
OPERATING PROCEDURES
1. SENSITIVITY LEVELS
55100 offers three sensitivity levels (Low-Med-High). It will detect leaks as low as 1/10 oz (3 grams) per
year. Turn
ON the unit, it will default to the Medium Level. (The Medium Level is the recommended setting to
begin inspection). To view the sensitivity level on the LED display, press either the
UP or DOWN arrow. The
LED display will illuminate for approximately two seconds. Two Red LEDS will progressively illuminate for
every sensitivity level.
The sensitivity level can be increased by the UP arrow and decreased by the DOWN arrow. Pressing the
selected arrow once will adjust the sensitivity to the next level. Pressing and holding the arrow will continue
to move the setting until the arrow is released.
2. DETECTION LEVELS
55100 offers 5 levels of detection. As the unit approaches the leak source and the refrigerant concentration
increases, the audible alarm will increase in speed and the LED will display 5 levels of detection.
The detection level will vary depending on the level of the sensitivity setting. The same size leak will display
higher detection levels in higher sensitivity settings and lower detection levels in the lower sensitivity
settings.
3. RESET FUNCTION
The primary use for the RESET function is to pinpoint the leak source. When the unit detects a leak and goes
into full alarm, press the
RESET button. Resetting will ignore any leaks at that level and only detect leaks of
higher concentration.
IMPORTANT LEAK DETECTION TIPS:
A. Make sure that the air conditioning/refrigeration system is turned OFF before inspection. A sufficient
amount of refrigerant must be present in the system. A minimum gauge pressure of 50 PSI at ambient
55100 Electronic Leak Detector
KEYPAD FUNCTION & PARTS
1. Turns unit ON and OFF
3. Increases Sensitivity
2. Resets Sensitivity Level
4. Decreases Sensitivity
to Zero Reference
5. Sensor Tip
BATTERY INSTALLATION
Hold the leak detector handle horizontally.
To remove the battery door, loosen the screw on top of the door and
pull the door away from the unit. Load the two “C” cell batteries into the
compartment with the positive (+) end up. Reinstall the battery door.
SENSITIVITY
Made in USA
���
����������
�������������
��
�����
GOOD / GREEN
LOW / YELLOW
REPLACE / RED
SENSITIVITY
Made in USA
���
����������
�������������
��
�����
Low Sensitivity
Setting
Medium
Sensitivity
Setting
High Sensitivity
Setting
SENSITIVITY
Made in USA
���
����������
�������������
��
�����
Detection Levels
Highest Levels
Table of Contents for MasterCool 55100:
-
2 SENSITIVITY Made in USA BATTERY TEST Turning the unit ON will automatically run the battery function test and display the battery condition on the UNITS LED display. To view the remaining battery life, press and hold the ON/OFF button. OPERATING PROCEDURES 1. SENSITIVITY LEVELS 55100 offers three sensitivity le
-
4 SENSITIVITY Made in USA BATTERIE TEST Bei Einschaltung “ON” des Elektronischen Lecksuchers werden Zustand und Funktion der Batterie automatisch auf der “LED” Anzeige angegeben. Um die Batterie zu prüfen, auf “ON/OFF” Knopf durchdrücken und halten. BEDIENUNGSVERFAHREN 1. SENSITIVITÄTSWERTE 55100 hat eine dreistufige Sensitivität (
-
6 SENSITIVITY Made in USA ESSAI DE LA BATTERIE La mise en marche “ON” du détecteur déclenche automatiquement le test de la batterie et affiche son état sur l’afficheur LED «DEL» à diodes luminescentes. Pour vérifier la charge restante de la batterie, appuyez et maintenez la touche «ON/OFF» en appui. PROCE
-
5 Manometerdruck bei einer Umgebungstemperatur von 15˚C (60˚F) oder darüber, und das System ausgeschaltet “OFF” ist für wirkungsvolle Lecksuchen unbedingt notwendig. B. Ein gutes Ergebnis erfolgt, wenn der Sensor bei einem Geschwindigkeits-Maßstab von 25-50mm pro Sekunde und 6mm Abstand in frischer Luft über die Lecksuchstelle geführt wird. Ein stärkeres Alarmsignal bedeutet eine Leckage. Um sich zu vergewissern, dass es sich tatsächlich um das Le
-
8 SENSITIVITY Made in USA COMPROBACIÓN DE LAS PILAS Poniendo la unidad en ON esta efectuará automáticamente la comprobación de las pilas y mostrará el estado de las mismas mediante diodos luminosos (LED.) Para verificar la carga disponible de las pilas. Pulsar y mantener el botón ON / OFF PROCEDIMIENTOS DE OPERACIÓN 1.
-
3 B. For the best leak detection results, the probe should be moved across the leak detection area at the rate of 1” — 2” per second (25 — 50mm per second) and held 1/4” (5mm) away from the surface. An increase in the alarm rate will indicate a leak. To confirm the correct leak location, blow shop air around the suspected leak area, move the probe into fresh air, reset and reinspect. C. When inspecting in contaminated or high humidity areas, erratic alarming ma
-
7 suffisante de réfrigérant doit se trouver dans le système. Pour une détection efficace une pression de minimum 50 PSI par température ambiante de 15˚C et davantage est requise à l’arrêt, position «OFF». B. Afin d’obtenir le meilleur résultat, déplacez la sonde le long de la zone de détection de fuite à une vitesse de 25-50mm (1”-2”) par seconde et gardez la à une distance de 6mm (1/4”) de la surface. Une alarme plus puissante indiquera une fuite. Pour localiser avec précision l’endroit de
-
10 SENSITIVITY Made in USA VERIFICA BATTERIA All’accensione dell’apparecchio si avvia automaticamente il test di efficienza della batteria, mostrando il livello di carica attraverso l’accensione dell’indicatore luminoso a LED. Per visualizzare la residua durata della batteria, tenere premuto il tasto ON/OFF. PROCEDURE OPERATIVE 1. LIVELLI DI SENSIBILITÀ 55100 offre tre livelli d
-
9 PSI a temperatura ambiente de 15˚C (60˚F) y superior con el sistema parado. B. Para unos mejores resultados en detección de fugas, la SONDA debe ser movida a lo largo de la zona de detección de fuga a una velocidad de 25-50mm (1”- 2”) por segundo y manteniendo una distancia de 5mm (1/4”) de la superficie. Un incremento de velocidad de la alarma indicará la fuga. Para confirmar la correcta situación de la fuga, pulverice aire comprimido alrededor de la zona de fuga sospechada y desplace la sonda dentro el
-
11 Nell’impianto deve essere presente una quantità sufficiente di refrigerante. Per un attendibile rilevamento delle fughe è necessaria, a impianto spento, una pressione di manometro minima di 50 PSI ad una temperatura ambiente di 60°F o superiore. B. Per ottenere un risultato ottimale nel rilevamento delle fughe, la sonda dovrebbe essere mossa nell’area da esplorare a 25-50 mm (1”- 2”) al secondo e tenuta ad una distanza di 5mm (1⁄4”) dalla superficie. La presenza di una perdita è segnalata dall’aumento della frequenza dell�
Questions, Opinions and Exploitation Impressions:
You can ask a question, express your opinion or share our experience of MasterCool 55100 device using right now.
Электронный течеискатель Mastercool 55100 — точный автономный детектор утечки хладагента. Выполнен в виде пистолета, имеет гибкий зонд, пять уровней настройки чувствительности, индикация светодиодная и звуковая. Управление осуществляется четырьмя кнопками на корпусе. Питание — две батарейки типа С. Поставляется в пластиковом кейсе. Предназначен для работы с CFC, HCFC, HFC хладагентами.
Документация
Купить
| Модель | 55100 |
| Производитель | Mastercool |
| Хладагенты | ГФУ, ГХФУ |
| Чувствительность | Скорость утечки ГФУ выше 3 г/год |
| Управление | 4 кнопки на корпусе |
| Длина гибкого зонда | 350 мм |